Polypropylene laminated paper (PPLP) and Kraft paper have been studied as multi-layer insulation for high temperature superconducting cable. The experiment was conducted with AC and impulse voltages. Short-term and long-term breakdown of insulation samples were investigated. The experimental results show that the breakdown voltage becomes smaller in the order of PPLP, PPLP/Kraft and Kraft, but the lifetime index increases with the presence of Kraft layer in the multilayer insulation. In addition, the position of PPLP layers has a significant effect on the breakdown voltage of PPLP/Kraft samples under positive impulse voltage. Finally, breakdown mechanism of PPLP/Kraft composite insulation was suggested. Partial discharges in butt-gaps and in the porous structure of insulation layers combined with electric discharges on the surface of these layers are considered to be main factors causing the puncture of multi-layer insulation.
Nguyễn Văn Dũng, 2015. Nghiên cứu ứng dụng công nghệ plasma lạnh trong xử lý nước: Tổng hợp tài liệu. Tạp chí Khoa học Trường Đại học Cần Thơ. 36: 106-111
Tạp chí: 2018 4th International Conference on Green Technology and Sustainable Development (GTSD), Ho Chi Minh City University of Technology and Education, November 23-24, 2018
Tạp chí khoa học Trường Đại học Cần Thơ
Lầu 4, Nhà Điều Hành, Khu II, đường 3/2, P. Xuân Khánh, Q. Ninh Kiều, TP. Cần Thơ
Điện thoại: (0292) 3 872 157; Email: tapchidhct@ctu.edu.vn
Chương trình chạy tốt nhất trên trình duyệt IE 9+ & FF 16+, độ phân giải màn hình 1024x768 trở lên